# Spray Foam Insulation for Cold Storage: Achieving High R-Values in Freezer Facilities

- [Ross Bahl](https://bahlfireproofing.com/author/rossbahl/)
- January 27, 2026
- 7:48 am

Freezer insulation using closed-cell spray polyurethane foam delivers R-6.0 to R-7.0 per inch thermal resistance enabling refrigerated warehouses and freezer facilities to achieve required thermal performance ranging from R-30 for coolers maintaining 32 to 55 degrees Fahrenheit to R-45 for freezers operating between negative 20 and 25 degrees Fahrenheit. Applications ranging from 4.6 to 7 inches meet cold storage design targets while simultaneously providing vapor barrier properties and air sealing, above the envelope minimum the adopted energy code sets for the climate zone. This triple functionality addresses the primary challenges facing cold storage operators including heat gain through building envelopes, moisture infiltration causing insulation degradation, and air leakage increasing refrigeration equipment runtime.

**TLDR:** Closed-cell spray foam insulation achieves R-6.0 to R-7.0 per inch thermal resistance meeting cold storage requirements of R-30 for coolers and R-45 for freezers with applications ranging from 4.6 to 7 inches thickness. Foam thickness exceeding two inches provides vapor barrier properties preventing moisture migration while monolithic application reduces air infiltration, which the Department of Energy estimates accounts for about 21 percent of heating and cooling energy in commercial buildings. [Spray foam insulation for cold storage](https://bahlfireproofing.com/spray-foam-insulation/) functions as primary thermal insulation system combining insulation, air barrier, and moisture barrier in single material unlike supplemental insulation products requiring separate vapor retarders. IBC (2021) Section 2603.4 requires a thermal barrier over spray foam in occupied spaces: one-half inch gypsum wallboard, heavy timber per IBC (2021) Section 602.4, or a material meeting the NFPA 275 acceptance criteria. A licensed mechanical engineer determines the complete envelope system against the adopted energy code, either ANSI/ASHRAE/IES Standard 90.1 Section 5.5 or IECC Section C402, plus vapor retarder specifications and local amendments. Trained applicators install spray foam at component temperatures between 60 and 90 degrees Fahrenheit requiring construction phase application or facility shutdown periods.

*Code note: unless otherwise stated, code references on this page are to the 2021 International Building Code. Code adoption is state and local. Across the states we serve, adopted IBC editions differ by state and by city, some states have no statewide commercial building code, and several enforce NFPA 1 or NFPA 101 rather than the International Fire Code. Minnesota and Wisconsin publish state-amended code books whose numbering and requirements differ from the model code. This is general technical information, not a code determination for your project. Confirm the adopted edition and any local amendments with your authority having jurisdiction.*

## Closed-Cell Foam for Moisture Barrier

Cold storage facilities operating below 40 degrees Fahrenheit face continuous moisture drive from warm humid exterior air toward cold interior surfaces where water vapor condenses. Moisture accumulation within insulation systems reduces thermal performance. Traditional insulation materials including fiberglass batts and mineral wool absorb moisture degrading thermal resistance. Cold storage design often calls for a Class I vapor retarder, 0.1 perm or less, on the warm side of the insulation assembly, as the building envelope consultant determines.

Closed-cell spray polyurethane foam applications exceeding two inches thickness function as vapor barriers eliminating need for separate vapor retarder materials in many building assemblies. Five-inch closed-cell foam achieves approximately 0.4 perm vapor permeance qualifying as Class II vapor retarder per building codes. Two and one-half inch applications deliver 0.8 perm vapor transmission rates. The material’s closed-cell structure prevents water vapor passage maintaining vapor barrier integrity throughout service life. Some cold storage designs require dedicated Class I vapor retarders with permeance below 0.1 perms which licensed building envelope consultants and mechanical engineers determine for specific applications.

Closed-cell foam’s moisture resistance extends beyond vapor transmission control. The material does not absorb liquid water maintaining thermal performance when exposed to condensation. Fiber-based insulation materials lose thermal resistance when wet requiring extended drying or replacement. Closed-cell foam’s impermeability prevents moisture absorption preserving R-value under adverse conditions.

Freezer facilities operating between negative 20 and negative 90 degrees Fahrenheit experience severe condensation risk. Warm humid air reaching subfreezing surfaces forms ice accumulation damaging insulation systems and structural components. Ice buildup on ceiling surfaces creates falling hazards endangering workers and products. Spray foam’s vapor control prevents moisture migration eliminating ice formation at critical interfaces.

Vapor barrier location proves critical in cold storage design. Building Science Corporation research emphasizes placing vapor retarders on warm sides of insulation assemblies. Exterior wall applications place foam against building envelope exterior providing proper vapor barrier location blocking moisture drive inward. Licensed building envelope consultants evaluate complete moisture management systems determining vapor barrier placement and penetration details.

## Extreme R-Values for Sub-Zero Temperatures

ANSI/ASHRAE/IES Standard 90.1 Section 5.5 sets envelope minimums by climate zone and assembly type, while facility operating temperature is a design criterion that sits on top of that minimum. Refrigerated warehouses maintaining interior temperatures between 32 and 55 degrees Fahrenheit require minimum R-30 roof insulation. Freezer facilities operating between negative 20 and 25 degrees demand minimum R-45 roof assemblies. California Title 24 energy code mandates minimum R-40 roof insulation and R-36 wall insulation for freezer applications.

Closed-cell spray polyurethane foam delivers R-6.0 to R-7.0 per inch thermal resistance tested per [ASTM C518 thermal transmission properties standards](https://store.astm.org/c0518-21.html). High-density closed-cell formulations achieve R-6.5 to R-8.0 per inch in specific applications. This thermal performance significantly exceeds open-cell spray foam providing R-3.5 to R-3.8 per inch and traditional batt insulation delivering R-3.0 to R-3.8 per inch. The superior R-value per inch enables thinner applications achieving required thermal resistance reducing material costs.

Closed-cell foam applications meeting cold storage requirements involve straightforward thickness calculations. Facilities requiring R-30 thermal resistance for cooler applications achieve specification with 4.6 to 5 inches closed-cell foam thickness. Freezer facilities demanding R-45 minimum insulation meet requirements with 6.4 to 7 inches foam thickness. California freezers requiring R-40 roof insulation achieve compliance with 5.7 to 7 inches depending on specific foam R-value.

Temperature differential between cold storage interiors and ambient conditions drives continuous heat transfer through building envelopes. Each Btu of heat entering refrigerated spaces requires compressor work to remove it and maintain design temperatures. Insufficient insulation forces refrigeration equipment to run longer and raises energy consumption. Cold storage operators processing temperature-sensitive pharmaceuticals, frozen foods, or industrial products cannot tolerate temperature fluctuations requiring consistent thermal barriers.

Aged R-value considerations affect long-term thermal performance specifications. Closed-cell foam R-value can decrease over time as blowing agents diffuse from cell structures, so the product data sheet gives both initial and aged R-values per inch. Licensed mechanical engineers specify foam thickness accounting for aged R-value ensuring facilities maintain required thermal resistance throughout service life. Conservative specifications prevent performance degradation requiring costly retrofits when insulation proves inadequate after aging effects manifest.

## Air Sealing for Refrigeration Efficiency

Air infiltration is a significant energy loss mechanism in commercial buildings, and in cold storage it introduces warm humid exterior air into refrigerated environments. Each cubic foot of infiltrating air at 90 degrees Fahrenheit and 60 percent relative humidity contains moisture and thermal energy requiring removal through refrigeration equipment. Uncontrolled air leakage increases refrigeration equipment runtime, raises energy costs, and compromises temperature stability.

Closed-cell spray foam applications create monolithic air barriers eliminating gaps and penetrations where air infiltration occurs. The material expands during application filling cracks, joints, and irregular surfaces producing continuous coverage. Traditional batt insulation compressed around obstacles leaves gaps permitting air movement. Spray foam’s seamless application addresses air leakage comprehensively throughout building envelopes.

Air sealing benefits extend beyond energy reduction. Cold storage facilities maintaining precise temperature ranges protect perishable products. Air infiltration introduces temperature fluctuations as warm exterior air enters refrigerated spaces. Spray foam air barriers improve temperature stability, enabling tighter temperature control. Pharmaceutical cold storage maintaining specific temperature ranges benefits substantially from enhanced environmental stability.

Energy efficiency improvements deliver measurable cost reductions. Air sealing lowers heating, cooling and refrigeration loads, and the size of the energy saving depends on the building, the climate and the existing leakage.

Refrigeration equipment capacity requirements decrease as air sealing reduces thermal loads. Compressors sized for facilities with high air infiltration losses operate continuously handling preventable loads. Reducing air leakage lowers compressor runtime, which reduces maintenance requirements and delays capital equipment replacement. Cold storage operators realize lifecycle cost advantages through extended compressor longevity and reduced service frequency.

Loading dock operations introduce significant air infiltration challenges. Refrigerated warehouses with many loading docks can see large air exchange volumes during peak operations. Spray foam air barriers around dock doors, overhead doors, and adjacent wall penetrations minimize infiltration at high-risk locations. Comprehensive sealing of electrical conduit penetrations, plumbing chases, and structural connections prevents air bypass around primary insulation systems maximizing refrigeration efficiency and protecting product quality.

## Preventing Thermal Bridging

Thermal bridging occurs where conductive materials bypass insulation creating preferential heat transfer paths. Structural steel framing, metal studs, and concrete slabs conduct heat substantially faster than insulation materials. Framing members conduct heat faster than cavity insulation, creating thermal bridges that reduce overall wall efficiency. Metal building systems experience severe thermal bridging through steel purlins, girts, and columns.

Continuous insulation strategies address thermal bridging by covering structural members with uninterrupted insulation layers. Adopted energy codes increasingly require continuous insulation independent of cavity insulation, through the opaque envelope tables of the IECC edition the jurisdiction has adopted or the equivalent 90.1 Section 5.5 assembly requirement. Closed-cell spray foam applied to building envelope exteriors or structural member exteriors provides continuous coverage eliminating thermal bridges. Applications covering steel beams, metal studs, and structural connections prevent conductive heat transfer improving overall assembly performance.

Interior spray foam applications behind studs reduce thermal bridging effects. One inch closed-cell foam behind wall framing delivers R-6.0 to R-7.0 thermal resistance keeping framing members warmer reducing heat loss. This continuous insulation layer supplements cavity insulation addressing the 25 percent wall area occupied by framing achieving superior thermal performance compared to cavity insulation alone.

Cold storage facilities utilizing metal building systems face substantial thermal bridging challenges. Steel purlins and girts supporting roof and wall panels create continuous thermal bridges from exterior to interior. Uninsulated metal building systems experience condensation on interior surfaces as steel members reach dew points. Spray foam covering structural steel eliminates thermal bridges preventing condensation while dramatically improving thermal performance. Applications to metal building interiors coat purlins, girts, columns, and roof deck creating comprehensive thermal barriers maintaining steel temperatures above dew point.

Concrete slab edges represent significant thermal bridges in cold storage facilities. Slab perimeters contact exterior soil and foundations providing heat transfer paths bypassing wall insulation. Uninsulated slab edges conducting heat from exterior grade through concrete introduce 15 to 25 Btu per linear foot per hour heat gain into freezer facilities. Closed-cell foam applied to slab edges and foundation walls eliminates edge thermal bridging. Underslab insulation combined with edge treatment provides comprehensive slab thermal control, with slab edge requirements set by the adopted energy code as an R-value at a stated depth or as an F-factor, not as a single whole-slab R-value. The slab edge insulation thickness and extent come from the adopted energy code and the engineer of record.

## Fire Code Requirements and Thermal Barriers

International Building Code IBC (2021) Section 2603 establishes fire safety requirements for foam plastic insulation in building applications. IBC (2021) Section 2603.3 requires foam plastic to have a flame spread index of 75 or less and a smoke-developed index of 450 or less per ASTM E84 or UL 723, tested at the maximum thickness intended for use. Class A interior finish, meaning a flame spread index of 25 or less, is a separate and stricter threshold that most spray foam products also meet. Typical closed-cell spray foam products achieve Flame Spread Index approximately 15 and Smoke Developed Index approximately 130 meeting Class A requirements.

Critical distinction exists between ASTM E84 surface burning tests and ASTM E119 fire-resistance rating tests. ASTM E84 evaluates material surface flame spread and smoke generation characteristics. ASTM E119 tests complete assemblies determining fire-resistance ratings measuring time structural elements withstand standard fire exposure maintaining load-bearing capacity. Spray foam meeting ASTM E84 Class A requirements does not provide structural fire protection and does not replace fire-rated construction assemblies required by building codes. Spray foam insulation serves as thermal insulation with excellent surface burning characteristics but does not protect structural steel from fire exposure requiring separate fireproofing systems.

International Building Code requires thermal barriers over foam plastic insulation in occupied spaces. Thermal barriers of one-half inch gypsum wallboard, heavy timber per IBC (2021) Section 602.4, or a material meeting the acceptance criteria of both the Temperature Transmission Fire Test and the Integrity Fire Test of NFPA 275 cover spray foam, delaying foam involvement in fires. Thermal barrier requirements apply to interior building spaces where occupants work or congregate. Unoccupied attics and crawl spaces may receive foam without thermal barriers under specific conditions detailed in IBC (2021) Section 2603.

Licensed fire protection engineers and building officials determine thermal barrier requirements for specific cold storage applications. Refrigerated warehouse areas with minimal human occupancy may qualify for reduced thermal barrier requirements compared to office areas. Authority having jurisdiction approval proves essential as jurisdictions interpret code requirements differently.

Fire suppression system interactions with spray foam insulation require evaluation. NFPA 13 sprinkler installation standards establish requirements based on building construction, occupancy classification, and combustible loading. Sprinkler requirements for a given cold storage building come from the adopted fire code and the licensed fire protection engineer. Cold storage facilities insured through FM Global should confirm the insurer’s requirements for foam plastic insulation with the insurer and the engineer of record.

## Multi-Story Cold Storage Is Named in the Code: NFPA 285 and the Freezer Envelope

A freezer envelope carries more foam than almost any other building, and cold storage appears in this provision by name. IBC (2021) Section 2603.5 covers exterior walls containing foam plastic insulation in buildings of Type I, II, III or IV construction, of any height, and it extends specifically to cold storage buildings required to be of noncombustible construction that are more than one story in height. Once a facility is in that scope, IBC (2021) Section 2603.5.5 requires that the exterior wall assembly be tested in accordance with and comply with the acceptance criteria of NFPA 285.

Cold storage also draws particular attention on the interior side, and that is where the confusion starts. Whatever accommodation a freezer wall earns under the thermal barrier provisions of IBC (2021) Section 2603.4 stays inside 2603.4. It does not carry across to 2603.5.5. The two subsections have separate triggers, and a project can clear the first while failing the second.

### The Panel Is Not the Compliance

NFPA 285 is the Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Wall Assemblies Containing Combustible Components, current edition 2025. It qualifies a complete exterior wall as one system: the foam or foam-core panel, its joints and fasteners, the barrier layers, the supporting framing, the cladding and the window head detail. This is an assembly test, not a product test. No foam and no insulated panel is NFPA 285 compliant on its own, and altering one element of the tested build-up can take the listing with it.

On refrigerated work the substitution risk usually lands on the joint or the attachment, because those are what get adjusted for thermal bridging and vapor sealing after the assembly was chosen. An insurer approval is a different finding too, answering a different question than the building official is asking under 2603.5.5.

### Surface Burning and the Interior Barrier

IBC (2021) Section 2603.3 holds foam plastic to a flame spread index of 75 or less and a smoke-developed index of 450 or less. The exterior wall version of that limit lives in IBC (2021) Section 2603.5.4: on Type I through IV construction, 25 or less flame spread with smoke developed unchanged at 450 or less, tested at the thickness intended for use up to 4 inches per ASTM E84 or UL 723. The thermal barrier under IBC (2021) Section 2603.4 is 1/2-inch gypsum wallboard, heavy timber complying with IBC (2021) Section 602.4, or a material meeting the acceptance criteria of both the Temperature Transmission Fire Test and the Integrity Fire Test of NFPA 275.

### What Falls Outside

- **Type V exterior walls**, which answer only to IBC (2021) Sections 2603.2, 2603.3 and 2603.4 and never reach 2603.5.
- **Exception 1.** One-story buildings complying with IBC (2021) Section 2603.4.1.4. Note how narrow that is here, given the section captures multi-story cold storage by name.
- **Exception 2.** Foam plastic covered on each face by not less than 1 inch of masonry or concrete, with either no airspace, or a flame spread index of 25 or less and an airspace not more than 1 inch.

Confirm construction type and story count first, then get the assembly listing in hand. Final determination rests with the engineer of record and the authority having jurisdiction.

## Key Takeaways

Closed-cell spray polyurethane foam delivers R-6.0 to R-7.0 per inch, letting cold storage facilities reach the R-30 cooler and R-45 freezer design targets at 4.6 to 7 inches, above the envelope minimum in the [adopted energy code](https://www.energycodes.gov/commercial-and-residential-building-energy-codes) for the project’s climate zone.

Foam applications exceeding two inches thickness provide vapor barrier properties with five-inch applications achieving approximately 0.4 perm vapor permeance qualifying as Class II vapor retarders eliminating need for separate vapor retarder materials in many assemblies while some cold storage designs require dedicated Class I vapor retarders below 0.1 perms determined by licensed building envelope consultants.

Monolithic spray foam applications reduce air infiltration, which lowers refrigeration equipment runtime and improves temperature stability.

Continuous insulation covering structural steel members, metal studs, and concrete slabs reduces thermal bridging, improving overall assembly thermal performance beyond cavity insulation R-values alone.

IBC (2021) Section 2603.4 requires a thermal barrier over spray foam in occupied spaces, prescriptively one-half inch gypsum wallboard or a material meeting the NFPA 275 acceptance criteria, with spray foam meeting the IBC (2021) Section 2603.3 limits of flame spread index 75 or less and smoke-developed index 450 or less, but not providing structural fire protection or ASTM E119 fire-resistance ratings.

[Building Science Corporation commercial spray foam guidelines](https://buildingscience.com/documents/guides-and-manuals/gm-2103-commercial-spray-foam-guide) establish professional installation requirements including trained applicators, component temperature maintenance between 60 and 90 degrees Fahrenheit, proper mixing ratios, thickness verification, and 24 to 48 hour off-gassing periods before occupancy.

[Cold storage spray foam insulation across Texas, Oklahoma, Kansas, Nebraska, Minnesota, Wisconsin, Arizona, Missouri, and Iowa](https://bahlfireproofing.com/service-areas/) requires closed-cell applications during construction phases or planned shutdown periods as substrate temperatures must reach 60 to 90 degrees Fahrenheit for proper foam adhesion and expansion preventing application during freezer operations.

If your refrigerated warehouse or freezer facility requires primary thermal insulation achieving R-30 to R-45 performance while providing integrated air barriers and vapor barriers, our own crews install the spray foam to meet the adopted energy code envelope requirement and the IBC Section 2603.4 thermal barrier requirement. [Contact Bahl Fireproofing for cold storage spray foam insulation solutions](https://bahlfireproofing.com/contact/) enhancing refrigeration efficiency through comprehensive building envelope thermal control.

**Disclaimer:** This article provides general educational information and does not constitute professional engineering advice or code compliance certification. Closed-cell spray polyurethane foam functions as primary thermal insulation and does not replace structural fireproofing protecting load-bearing steel or fire-rated assemblies. Spray foam provides ASTM E84 Class A surface burning characteristics but does not provide ASTM E119 fire-resistance ratings and does not replace spray-applied fire-resistive materials or intumescent coatings. International Building Code IBC (2021) Section 2603 requires thermal barriers consisting of minimum one-half inch gypsum board over spray foam in occupied spaces. Closed-cell spray foam required for cold storage applications with open-cell foam inappropriate due to moisture absorption. Licensed mechanical engineer, fire protection engineer, building envelope consultant, and authority having jurisdiction determine complete insulation systems, thermal barrier requirements, vapor barrier specifications, R-value requirements, sprinkler system design, and application specifications for cold storage facilities. R-value requirements vary by climate zone and assembly per the adopted energy code, either ANSI/ASHRAE/IES Standard 90.1 Section 5.5 or IECC Section C402, in the edition the AHJ enforces. Installation by trained applicators required with component temperatures between 60 and 90 degrees Fahrenheit preventing application on freezer-temperature substrates. Performance and cost vary by foam type, thickness, application conditions, climate zone, and project specifics. Always consult licensed professionals to verify building code requirements and complete system specifications.

Written for Bahl Fireproofing**Ross Bahl, Owner**

Ross owns Bahl Fireproofing, the commercial fireproofing and insulation subcontractor his family started in 1977. Every code figure on this site is checked against the published source before it goes up. [More about Ross](/ross-bahl/).

[PrevPreviousK-13 Insulation for Cold Storage: Thermal and Acoustic Performance in Refrigerated Facilities](https://bahlfireproofing.com/k-13-insulation-for-cold-storage-thermal-and-acoustic-performance-in-refrigerated-facilities/)

[NextIntumescent Fireproofing for Cold Storage: Protecting Steel in Freezer FacilitiesNext](https://bahlfireproofing.com/intumescent-fireproofing-for-cold-storage-protecting-steel-in-freezer-facilities/)

On this page

Bidding this scope?**Send us the drawings.**

Spray-applied fireproofing, intumescent coatings, K-13, spray foam and Core Foam, self-performed across nine states. We price the assembly on your drawings, not a square-foot guess.

[Request a bid](/contact/)[Call the office512-387-2111](tel:512-387-2111)

### Have a rated assembly to cover?

Send the drawings and the spec section. We come back with the scope in and the scope out stated plainly, so your bid tab compares the same work across every subcontractor on it.

[Call the office512-387-2111](tel:512-387-2111)[Request a bid](/contact/)

## Keep reading

### [K-13 Insulation: Built for Long-Term Performance](https://bahlfireproofing.com/k-13-insulation-built-for-long-term-performance/)

October 23, 2025

Commercial buildings demand insulation systems that deliver reliable thermal and acoustic performance over decades of service. K-13 spray-applied cellulose insulation addresses this

 [Read the guide](https://bahlfireproofing.com/k-13-insulation-built-for-long-term-performance/)

### [School Masonry Insulation: The Complete Core Foam Guide](https://bahlfireproofing.com/school-masonry-insulation-core-foam/)

September 23, 2026

Most school buildings across Texas, Kansas, and Oklahoma are concrete block, and in the older ones the cores are empty. School masonry

 [Read the guide](https://bahlfireproofing.com/school-masonry-insulation-core-foam/)

### [Cold Storage Fireproofing: Fire Protection in Temperature-Controlled Facilities](https://bahlfireproofing.com/cold-storage-fireproofing-fire-protection-in-temperature-controlled-facilities/)

January 21, 2026

Cold storage fireproofing protects structural steel in refrigerated warehouses and freezer facilities operating at temperatures ranging from negative 30 degrees Fahrenheit to

 [Read the guide](https://bahlfireproofing.com/cold-storage-fireproofing-fire-protection-in-temperature-controlled-facilities/)

```json
{"@context":"https:\/\/schema.org","@graph":[{"@type":"Service","@id":"https:\/\/bahlfireproofing.com\/spray-foam-insulation-for-cold-storage-achieving-high-r-values-in-freezer-facilities\/#industry","name":" Fireproofing","url":"https:\/\/bahlfireproofing.com\/spray-foam-insulation-for-cold-storage-achieving-high-r-values-in-freezer-facilities\/","serviceType":"Commercial Fireproofing","provider":{"@id":"https:\/\/bahlfireproofing.com\/#organization"},"areaServed":[{"@type":"State","name":"Texas"},{"@type":"State","name":"Oklahoma"},{"@type":"State","name":"Kansas"},{"@type":"State","name":"Arizona"},{"@type":"State","name":"Wisconsin"},{"@type":"State","name":"Minnesota"},{"@type":"State","name":"Nebraska"},{"@type":"State","name":"Missouri"},{"@type":"State","name":"Iowa"}],"isRelatedTo":[{"@type":"Service","name":"Intumescent Fireproofing","url":"https:\/\/bahlfireproofing.com\/intumescent-fireproofing\/"},{"@type":"Service","name":"Spray-Applied Fireproofing","url":"https:\/\/bahlfireproofing.com\/fireproofing\/"},{"@type":"Service","name":"Cementitious Fireproofing","url":"https:\/\/bahlfireproofing.com\/cementitious-fireproofing\/"}]},{"@type":"BlogPosting","@id":"https:\/\/bahlfireproofing.com\/spray-foam-insulation-for-cold-storage-achieving-high-r-values-in-freezer-facilities\/#blogposting","headline":"Cold Storage Insulation: How Closed-Cell Spray Foam Performs","description":"Cold storage insulation with closed-cell spray foam: moisture control, air sealing, thermal bridging, and fire code and thermal barrier rules.","url":"https:\/\/bahlfireproofing.com\/spray-foam-insulation-for-cold-storage-achieving-high-r-values-in-freezer-facilities\/","datePublished":"2026-01-27T07:48:00-06:00","dateModified":"2026-10-24T17:33:14-05:00","image":{"@type":"ImageObject","url":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2026\/01\/MedicalBuilding-Insulation-3.png"},"author":{"@type":"Person","@id":"https:\/\/bahlfireproofing.com\/ross-bahl\/#person","name":"Ross Bahl","url":"https:\/\/bahlfireproofing.com\/ross-bahl\/","jobTitle":"Owner"},"publisher":{"@type":"Organization","@id":"https:\/\/bahlfireproofing.com\/#organization","name":"Bahl Fireproofing, LLC","url":"https:\/\/bahlfireproofing.com\/","logo":{"@type":"ImageObject","url":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2025\/02\/7ae06-be6a6e71-7409-4c8c-bc8b-c64bc18f6b39-removebg-preview.png"}},"mainEntityOfPage":{"@type":"WebPage","@id":"https:\/\/bahlfireproofing.com\/spray-foam-insulation-for-cold-storage-achieving-high-r-values-in-freezer-facilities\/"},"articleSection":"Spray Foam Insulation","keywords":"Cold storage, Energy efficiency","about":[{"@type":"Thing","name":"Commercial Fireproofing"},{"@type":"Thing","name":"Fire-Resistive Construction"}],"name":"Cold Storage Insulation: How Closed-Cell Spray Foam Performs"},{"@type":"Organization","@id":"https:\/\/bahlfireproofing.com\/#organization","name":"Bahl Fireproofing","sameAs":["https:\/\/network.procore.com\/p\/bahl-fireproofing-llc-round-rock","https:\/\/subcontractorsaustintexas.com\/company\/bahl-fireproofing-llc\/","https:\/\/www.yelp.com\/biz\/bahl-fireproofing-round-rock","https:\/\/www.buzzfile.com\/business\/Bahl-Fireproofing-LLC-512-387-2111","https:\/\/members.asaonline.com\/directory\/Details\/bahl-fireproofing-llc-2594032","https:\/\/www.manta.com\/c\/mm70y4c\/bahl-fireproofing-inc","https:\/\/www.nfca-online.org\/index.php?option=com_community&amp;view=profile&amp;userid=2018789809&amp;module=view-all&amp;uuid=f0c1d73b-33e3-4f07-bc9a-acef2520da51&amp;current_page=0&amp;directory_search_id=2006651#\/profile"],"logo":{"@type":"ImageObject","@id":"https:\/\/bahlfireproofing.com\/#logo","url":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2025\/02\/7ae06-be6a6e71-7409-4c8c-bc8b-c64bc18f6b39-removebg-preview.png","contentUrl":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2025\/02\/7ae06-be6a6e71-7409-4c8c-bc8b-c64bc18f6b39-removebg-preview.png","caption":"Bahl Fireproofing","inLanguage":"en-US","width":"312","height":"59"}},{"@type":"WebSite","@id":"https:\/\/bahlfireproofing.com\/#website","url":"https:\/\/bahlfireproofing.com","name":"Bahl Fireproofing","alternateName":"Bahl Fireproofing LLC","publisher":{"@id":"https:\/\/bahlfireproofing.com\/#organization"},"inLanguage":"en-US"},{"@type":"ImageObject","@id":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2026\/01\/MedicalBuilding-Insulation-3.png","url":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2026\/01\/MedicalBuilding-Insulation-3.png","width":"1024","height":"1024","caption":"Spray Foam Insulation for Cold Storage: Achieving High R-Values in Freezer Facilities","inLanguage":"en-US"},{"@type":"BreadcrumbList","@id":"https:\/\/bahlfireproofing.com\/spray-foam-insulation-for-cold-storage-achieving-high-r-values-in-freezer-facilities\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":"1","item":{"@id":"https:\/\/bahlfireproofing.com","name":"Home"}},{"@type":"ListItem","position":"2","item":{"@id":"https:\/\/bahlfireproofing.com\/blog\/","name":"Blog"}},{"@type":"ListItem","position":"3","item":{"@id":"https:\/\/bahlfireproofing.com\/category\/spray-foam-insulation-blog\/","name":"Spray Foam Insulation"}},{"@type":"ListItem","position":"4","item":{"@id":"https:\/\/bahlfireproofing.com\/spray-foam-insulation-for-cold-storage-achieving-high-r-values-in-freezer-facilities\/","name":"Spray Foam Insulation for Cold Storage: Achieving High R-Values in Freezer Facilities"}}]},{"@type":"WebPage","@id":"https:\/\/bahlfireproofing.com\/spray-foam-insulation-for-cold-storage-achieving-high-r-values-in-freezer-facilities\/#webpage","url":"https:\/\/bahlfireproofing.com\/spray-foam-insulation-for-cold-storage-achieving-high-r-values-in-freezer-facilities\/","name":"Cold Storage Insulation: How Closed-Cell Spray Foam Performs","datePublished":"2026-01-27T07:48:00-06:00","dateModified":"2026-10-24T17:33:14-05:00","isPartOf":{"@id":"https:\/\/bahlfireproofing.com\/#website"},"primaryImageOfPage":{"@id":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2026\/01\/MedicalBuilding-Insulation-3.png"},"inLanguage":"en-US","breadcrumb":{"@id":"https:\/\/bahlfireproofing.com\/spray-foam-insulation-for-cold-storage-achieving-high-r-values-in-freezer-facilities\/#breadcrumb"}}]}
```