# Fireproofing Inspection Checklist for Building Owners

- [Ross Bahl](https://bahlfireproofing.com/author/rossbahl/)
- August 6, 2026
- 10:00 am

![Fireproofing inspection checklist for building owners](https://bahlfireproofing.com/wp-content/uploads/2026/06/360da32b-820d-4445-b1e5-a2ad9a5fd33e-1024x1024.png)Fireproofing inspection checklist for building owners 2

Fireproofing protects your structural steel for the life of the building, but it does not take care of itself. Trades knock it off, renovations disturb it, and water and abrasion wear it down, and nobody notices until an inspector or a fire does. This is a practical fireproofing inspection checklist for building owners and facility managers to keep existing fireproofing intact, separate from the one-time special inspection performed during construction.

**TLDR:** The fireproofing inspection that matters most is the one that happens after the building opens. The code-mandated special inspection only confirms the fireproofing was correct on day one; keeping it correct over the building’s life is the owner’s job, and most in-service fireproofing damage stays invisible until someone looks above the ceiling. This fireproofing inspection checklist covers what to check, where to look, how often, what to document, and when to call a professional.

Picture a steel beam above a drop ceiling where an HVAC contractor knocked the fireproofing loose during a tenant fit-out two years ago and never patched it. The bare steel has been sitting there, unprotected, ever since, which means the fire-resistance rating that assembly was built to has been compromised the entire time. The construction special inspection signed off years ago, the certificate of occupancy is framed on the wall, and no one has looked above that ceiling since. That gap is exactly what an owner’s inspection routine exists to catch.

## Why Building Owners Need an Ongoing Fireproofing Inspection

Building owners need an ongoing fireproofing inspection because the special inspection performed at construction only verifies the fireproofing was correct when the building opened. Over the building’s life, MEP work, renovations, water, and abrasion damage it, and because most fireproofing sits above ceilings and out of sight, that damage goes unnoticed until it is found by a re-inspection, an insurer, or a fire. Keeping the protection intact after occupancy is the owner’s responsibility, not the original inspector’s.

That responsibility is easy to overlook precisely because fireproofing is passive and hidden. It does its job silently for decades, which makes it simple to forget until something forces the issue. A periodic owner inspection turns that hidden system into something you actually verify, instead of something you assume is fine. It is the difference between knowing your [fireproofing](https://bahlfireproofing.com/fireproofing/) is intact and hoping it is.

## Construction Inspection Versus Ongoing Inspection: Know the Difference

These are two different things, and confusing them is how buildings end up unprotected. The construction special inspection, required by [IBC Section 1705.15](https://codes.iccsafe.org/content/IBC2021P1/chapter-17-special-inspections-and-tests), is a one-time, code-mandated verification of thickness, density, and bond strength, performed by a qualified special inspector before the certificate of occupancy is issued. It proves the installation met the approved documents on the day it was done.

The ongoing inspection is something else entirely: the owner’s periodic check that the fireproofing is still there and still intact years later. The first inspection gets you occupancy; the second keeps you protected. This checklist is about the second, the one that has no certificate riding on it and that, for that reason, is the one most likely to be skipped. For the details of the construction-phase process, the inspection-process guide linked at the end covers it in full.

## What Damages Fireproofing After the Building Opens

Over the past 20 years inspecting commercial buildings across Texas, Kansas, and Oklahoma, the damage I find above ceilings almost always traces to work that happened after the building opened, not to bad original application. MEP trades are the biggest culprit: an electrician, plumber, or HVAC tech runs a new line through a fireproofed beam or deck, knocks material loose, and moves on without patching it. Renovations and tenant fit-outs disturb it the same way, often years apart, so the damage accumulates.

Water is the second pattern. A roof or plumbing leak saturates fireproofing, and certain materials lose bond or degrade when they stay wet, leaving sagging or crumbling protection over corroding steel. Abrasion and impact in mechanical rooms, storage areas, and high-traffic zones wear material away, and vibration near equipment can loosen it over time. None of these announce themselves, which is why a deliberate look is the only way to find them.

## The Fireproofing Inspection Checklist: What to Check and Where

A useful fireproofing inspection checklist works through the building’s fire-rated steel systematically rather than glancing around. Start with where the fireproofing actually is: above ceiling tiles at beams, columns, and connections, on the underside of floor and roof deck, around every MEP penetration, and in mechanical rooms and high-traffic areas where physical damage is likely. Pull ceiling tiles in a representative sample of spaces rather than assuming what you cannot see is fine.

Work through this checklist at each location:

- **Bare steel.** Any spot where material is missing or knocked off, exposing uncoated steel, is a compromised assembly.
- **Unpatched penetrations.** Gaps and open areas around newly run pipes, conduit, or duct where trades cut through and did not restore the fireproofing.
- **Cracks, delamination, or sagging.** Material separating from the steel, cracking, or hanging loose has lost the bond it needs to perform.
- **Water damage.** Staining, dampness, or visible corrosion under or around the fireproofing points to a leak and possible material degradation.
- **Removed or thinned material.** Areas where trades scraped, crushed, or compressed the fireproofing, including overspray that was cleaned off and never reapplied.
- **Traffic and impact damage.** Crushed or gouged material in storage, mechanical, and high-use areas.

Photograph anything questionable with its location noted, so the condition can be tracked and shown to a professional. The checklist identifies problems; it does not fix them.

## How Often Should You Inspect, and What Triggers a Check

A reasonable baseline is a periodic walk-through of representative areas, but the more important inspections are event-driven. Inspect after any work that happened above the ceiling or near the structure, because that is when most damage occurs. Inspect after any water event, since leaks are the second leading cause of failure. And inspect before a tenant turnover or fit-out, both to document the existing condition and because the incoming work is likely to disturb the steel again.

The principle is simple: any time someone has been working in the ceiling or the structure has been wet, assume the fireproofing may have been affected and verify it. Treating those events as inspection triggers catches the damage close to when it happened, while the responsible party may still be on record, rather than discovering it years later with no idea who did it.

## What an Intact Assembly Actually Protects

The reason any of this matters is that fireproofing is rated as part of a tested assembly, not as a coating in isolation. A fire-resistance rating is established by testing the complete assembly to [ASTM E119](https://store.astm.org/e0119-24.html), and that rating assumes the fireproofing is present and intact at the specified thickness. Strip a section of it off, and that part of the assembly is no longer the rated assembly: a two-hour beam with a bare patch is not a two-hour beam anymore.

That is why a small area of missing material is not a cosmetic issue. In a fire, steel loses strength as it heats, and the fireproofing is what slows that heating long enough for people to evacuate and the structure to hold. A gap in the protection is a gap in exactly the place the rating was counting on, which is what makes finding and restoring damage worth the effort of looking.

## Documentation: The Records Every Owner Should Keep

An inspection is only as useful as the records behind it. Keep the original special-inspection reports from construction, the as-built fireproofing specifications (the product, the required thickness, and the assemblies used), photographs of current conditions, and a running log of any damage found and repairs made. Those documents are what a future special inspector, an insurer, or a prospective buyer will ask for, and reconstructing them after the fact is far harder than maintaining them.

Good documentation also makes each inspection faster and more accurate, because you can compare current conditions to a known baseline and to your required thicknesses rather than guessing. For an owner, that record is the proof that the building’s fire protection has been maintained, not just installed, which is increasingly what diligence on a commercial property looks like.

## When to Call a Professional: From Checklist to Repair

The owner’s checklist identifies; a qualified professional verifies and repairs. Bring in a qualified fireproofing contractor whenever you find bare steel, unpatched penetrations, water-damaged material, or anything you are unsure about. Repairs have to restore the assembly with the correct listed material at the right thickness, not just fill the gap with whatever is handy, and field verification, thickness and density per ASTM E605 and bond strength per [ASTM E736](https://store.astm.org/e0736_e0736m-19r23.html), confirms the repair actually performs.

Access and safety are part of this step, since proper inspection and repair of overhead fireproofing often require lifts, ladders, and ceiling access that a casual look does not. The handoff is clean: you walk the building and document what you find, and a professional brings the testing, the listed materials, and the equipment to put the protection back to its rated condition. The repair guide and inspection-process guide linked below cover what that work involves.

## Fireproofing Inspection for Building Owners in Texas, Kansas, and Oklahoma

Across our Texas, Oklahoma, Kansas, Nebraska, Minnesota, and Wisconsin service area, the buildings most often carrying undetected fireproofing damage are the ones that have been through tenant turnovers, expansions, or roof repairs, common in active commercial and industrial markets. The practical move for owners and facility managers is to build this fireproofing inspection checklist into the building’s routine, especially as an automatic step after any ceiling work or water event. Catching and restoring damage early is far cheaper than discovering it during a sale, a re-inspection, or an emergency, which is the work our team handles for owners [throughout our service area](https://bahlfireproofing.com/texas/).

## Frequently Asked Questions

**Why do building owners need an ongoing fireproofing inspection?** Because the special inspection at construction only confirms the fireproofing was correct on opening day. MEP work, renovations, water, and abrasion damage it over time, and since it sits above ceilings out of sight, that damage goes unnoticed until a re-inspection or a fire finds it. Maintaining the protection is the owner’s responsibility.

**Is an in-service fireproofing inspection required by code?** The special inspection during construction is code-mandated under IBC (2021) Section 1705.15 (Section 1705.14 in the 2018 and earlier editions). Ongoing in-service inspection is part of the owner’s broader responsibility to maintain the building’s fire protection, and while the framework varies by jurisdiction, leaving damaged fireproofing unaddressed means the rated assembly is no longer performing as required.

**Where is fireproofing damage usually found?** Above ceiling tiles at beams, columns, and connections, on the underside of floor and roof deck, and around MEP penetrations where trades have run new lines. Mechanical rooms and high-traffic areas are also common, because that is where physical impact and abrasion occur.

**How often should fireproofing be inspected?** A periodic baseline walk-through plus event-driven checks. Inspect after any work above the ceiling, after any water event, and before a tenant turnover or fit-out, because those are the moments when fireproofing is most likely to have been disturbed or damaged.

**What does damaged fireproofing actually affect?** It compromises the fire-resistance rating of the assembly, which is established by testing the complete assembly to ASTM E119 with the fireproofing intact. A section of missing material means that part of the structure no longer carries its rated protection, so a two-hour assembly with bare steel is no longer a two-hour assembly.

**Can I inspect fireproofing myself?** Owners and facility managers can and should visually check and document conditions using a checklist like this one. Verifying and repairing damage, including field testing for thickness, density, and bond, is work for a qualified fireproofing contractor, so the owner’s role is to find and record problems and then bring in a professional.

**What should I do if I find damaged fireproofing?** Document it with photos and location notes, and bring in a qualified fireproofing contractor to restore the assembly with the correct listed material at the proper thickness. Do not ignore it or patch it with an unlisted product, because either leaves the assembly’s fire rating compromised.

## Key Takeaways

- **The inspection that matters is after opening.** The construction special inspection confirms day-one condition; keeping fireproofing intact over the building’s life is the owner’s job.
- **Most damage is post-construction and hidden.** MEP work, renovations, water, and abrasion cause it, and it sits above ceilings where no one looks.
- **Know where to look.** Beams, columns, connections, deck undersides, MEP penetrations, and mechanical and high-traffic areas.
- **Use event triggers.** Inspect after any ceiling work, any water event, and before tenant turnovers, not just on a calendar.
- **Damage breaks the rating.** Fireproofing is rated as part of an ASTM E119 assembly, so bare steel means that section is no longer its rated assembly.
- **Keep the records.** Original inspection reports, as-built specs, photos, and a repair log are what inspectors, insurers, and buyers will want.
- **Hand off to a professional.** Owners find and document; a qualified contractor restores the assembly with listed material and confirms it with field testing.

## Related Reading

- Want the construction-phase process? Read [the fireproofing inspection process](https://bahlfireproofing.com/the-fireproofing-inspection-process-a-complete-guide-for-building-owners/) for what happens before occupancy.
- Found damage from trades? See our [fireproofing repair after MEP trades guide](https://bahlfireproofing.com/fireproofing-repair-after-mep-trades-guide/) for how restoration works.
- Need the code basics? Review [commercial fireproofing requirements for building owners](https://bahlfireproofing.com/commercial-fireproofing-requirements-what-building-owners-must-know/).

If you own or manage a commercial building and have never looked above the ceiling at your fireproofing, the work is straightforward: walk the rated steel with this checklist, document what you find, and bring in a professional to restore anything that is damaged. That is work our crew handles throughout Texas, Oklahoma, Kansas, Nebraska, Minnesota, and Wisconsin. Reach me directly at 512-387-2111 or [ross@bahlfireproofing.com](mailto:ross@bahlfireproofing.com), or [Contact Bahl Fireproofing](https://bahlfireproofing.com/contact/) to schedule an assessment of your building’s fire protection.

*This article provides general educational information about inspecting in-service commercial fireproofing. It is not engineering advice and does not replace the code-required special inspections performed by qualified special inspectors meeting IBC criteria, nor repair and field testing performed by qualified professionals. An owner’s visual self-inspection supplements but does not satisfy code-mandated inspection requirements. Inspection intervals, responsibilities, and repair requirements vary by jurisdiction and by the specific rated assemblies in your building. Always confirm fire-protection inspection and maintenance obligations with the authority having jurisdiction and a licensed architect or engineer before relying on any inspection or repair approach.*

Written for Bahl Fireproofing**Ross Bahl, Owner**

Ross owns Bahl Fireproofing, the commercial fireproofing and insulation subcontractor his family started in 1977. Every code figure on this site is checked against the published source before it goes up. [More about Ross](/ross-bahl/).

[PrevPreviousK-13 Acoustic Performance: NRC Ratings by Thickness](https://bahlfireproofing.com/k-13-acoustic-performance-nrc-ratings/)

[NextFireproofing for Restaurants and Commercial KitchensNext](https://bahlfireproofing.com/fireproofing-for-restaurants-and-commercial/)

#### On this page

Bidding this scope?**Send us the drawings.**

Spray-applied fireproofing, intumescent coatings, K-13, spray foam and Core-Fill, self-performed across six states. We price the assembly on your drawings, not a square-foot guess.

[Request a bid](/contact/)[Call the office512-387-2111](tel:512-387-2111)

### Have a rated assembly to cover?

Send the drawings and the spec section. We come back with the scope in and the scope out stated plainly, so your bid tab compares the same work across every subcontractor on it.

[Call the office512-387-2111](tel:512-387-2111)[Request a bid](/contact/)

## Keep reading

### [When Does Spray Foam Need a Thermal Barrier? IBC 2603 Explained](https://bahlfireproofing.com/when-does-spray-foam-need-a-thermal-barrier/)

July 21, 2026

Spray foam is an excellent insulator, but the building code does not treat it as just insulation. Because it is a foam

 [Read the guide](https://bahlfireproofing.com/when-does-spray-foam-need-a-thermal-barrier/)

### [SFRM Special Inspection: What IBC Chapter 17 Requires for Spray Fireproofing](https://bahlfireproofing.com/sfrm-special-inspection-what-ibc-17-requires/)

July 9, 2026

Spray-applied fireproofing on structural steel is one of the building elements the code singles out for independent, third-party special inspection. This guide

 [Read the guide](https://bahlfireproofing.com/sfrm-special-inspection-what-ibc-17-requires/)

### [ASTM E119 vs UL 263: What’s the Difference for Commercial Fireproofing?](https://bahlfireproofing.com/astm-e119-vs-vl-263-difference-fireproofing/)

July 1, 2026

If you are specifying, bidding, or inspecting fireproofing on a commercial steel building, you have seen both ASTM E119 and UL 263

 [Read the guide](https://bahlfireproofing.com/astm-e119-vs-vl-263-difference-fireproofing/)

### [Texas Fire Code for Commercial Construction: What Actually Governs Your Fireproofing](https://bahlfireproofing.com/texas-fire-code-for-commercial-construction/)

July 13, 2026

If you are looking for “the Texas fire code” to find out what fireproofing your commercial project needs, the honest answer is

 [Read the guide](https://bahlfireproofing.com/texas-fire-code-for-commercial-construction/)

### [SFRM Density Categories: Low, Medium, and High Density Explained](https://bahlfireproofing.com/sfrm-density-categories-explained/)

April 3, 2026

Spray-applied fire-resistive material (SFRM) comes in three density categories, and the one your project specifies determines how well the fireproofing survives on

 [Read the guide](https://bahlfireproofing.com/sfrm-density-categories-explained/)

### [Intumescent Coating Maintenance and Inspection: A Field Guide for Building Owners and Facility Managers](https://bahlfireproofing.com/intumescent-coating-maintenance-inspection/)

June 19, 2026

Intumescent coatings can be one of the most dependable forms of passive fire protection for exposed structural steel. Applied correctly, they hold

 [Read the guide](https://bahlfireproofing.com/intumescent-coating-maintenance-inspection/)

```json
{"@context":"https:\/\/schema.org","@graph":[{"@type":"Service","@id":"https:\/\/bahlfireproofing.com\/fireproofing-checklist-for-building-owners\/#industry","name":" Fireproofing","url":"https:\/\/bahlfireproofing.com\/fireproofing-checklist-for-building-owners\/","serviceType":"Commercial Fireproofing","provider":{"@id":"https:\/\/bahlfireproofing.com\/#organization"},"areaServed":[{"@type":"State","name":"Texas"},{"@type":"State","name":"Oklahoma"},{"@type":"State","name":"Kansas"},{"@type":"State","name":"Arizona"},{"@type":"State","name":"Wisconsin"},{"@type":"State","name":"Minnesota"},{"@type":"State","name":"Nebraska"}],"isRelatedTo":[{"@type":"Service","name":"Intumescent Fireproofing","url":"https:\/\/bahlfireproofing.com\/intumescent-fireproofing\/"},{"@type":"Service","name":"Spray-Applied Fireproofing","url":"https:\/\/bahlfireproofing.com\/fireproofing\/"},{"@type":"Service","name":"Cementitious Fireproofing","url":"https:\/\/bahlfireproofing.com\/cementitious-fireproofing\/"}]},{"@type":"BlogPosting","@id":"https:\/\/bahlfireproofing.com\/fireproofing-checklist-for-building-owners\/#blogposting","headline":"Fireproofing Inspection Checklist For Building Owners - Bahl Fireproofing","description":"The fireproofing inspection that matters most is the one that happens after the building opens. The code-mandated special inspection only...","url":"https:\/\/bahlfireproofing.com\/fireproofing-checklist-for-building-owners\/","datePublished":"2026-08-06T10:00:00-05:00","dateModified":"2026-09-25T12:17:36-05:00","image":{"@type":"ImageObject","url":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2026\/06\/360da32b-820d-4445-b1e5-a2ad9a5fd33e.png"},"author":{"@type":"Person","@id":"https:\/\/bahlfireproofing.com\/ross-bahl\/#person","name":"Ross Bahl","url":"https:\/\/bahlfireproofing.com\/ross-bahl\/","jobTitle":"Owner"},"publisher":{"@type":"Organization","@id":"https:\/\/bahlfireproofing.com\/#organization","name":"Bahl Fireproofing, LLC","url":"https:\/\/bahlfireproofing.com\/","logo":{"@type":"ImageObject","url":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2025\/02\/7ae06-be6a6e71-7409-4c8c-bc8b-c64bc18f6b39-removebg-preview.png"}},"mainEntityOfPage":{"@type":"WebPage","@id":"https:\/\/bahlfireproofing.com\/fireproofing-checklist-for-building-owners\/"},"articleSection":"Fireproofing","keywords":"Codes and inspection, Maintenance and repair","about":[{"@type":"Thing","name":"Commercial Fireproofing"},{"@type":"Thing","name":"Fire-Resistive Construction"}],"name":"Fireproofing Inspection Checklist For Building Owners - Bahl Fireproofing"},{"@type":"BreadcrumbList","@id":"https:\/\/bahlfireproofing.com\/fireproofing-checklist-for-building-owners\/#breadcrumb","itemListElement":[{"@type":"ListItem","name":"Home","item":"https:\/\/bahlfireproofing.com\/","position":"1"},{"@type":"ListItem","name":"Blog","item":"https:\/\/bahlfireproofing.com\/blog\/","position":"2"},{"@type":"ListItem","name":"Fireproofing Inspection Checklist For Building Owners - Bahl Fireproofing","item":"https:\/\/bahlfireproofing.com\/fireproofing-checklist-for-building-owners\/","position":"3"}]},{"@type":["Person","Organization"],"@id":"https:\/\/bahlfireproofing.com\/#person","name":"Bahl Fireproofing","sameAs":["https:\/\/network.procore.com\/p\/bahl-fireproofing-llc-round-rock","https:\/\/subcontractorsaustintexas.com\/company\/bahl-fireproofing-llc\/","https:\/\/www.yelp.com\/biz\/bahl-fireproofing-round-rock","https:\/\/www.buzzfile.com\/business\/Bahl-Fireproofing-LLC-512-387-2111","https:\/\/subcontractorsaustintexas.com\/company\/bahl-fireproofing-llc\/","https:\/\/members.asaonline.com\/directory\/Details\/bahl-fireproofing-llc-2594032","https:\/\/www.osha.gov\/ords\/imis\/establishment.inspection_detail?id=303410971","https:\/\/www.manta.com\/c\/mm70y4c\/bahl-fireproofing-inc","https:\/\/www.nfca-online.org\/index.php?option=com_community&amp;view=profile&amp;userid=2018789809&amp;module=view-all&amp;uuid=f0c1d73b-33e3-4f07-bc9a-acef2520da51&amp;current_page=0&amp;directory_search_id=2006651#\/profile"],"logo":{"@type":"ImageObject","@id":"https:\/\/bahlfireproofing.com\/#logo","url":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2025\/02\/7ae06-be6a6e71-7409-4c8c-bc8b-c64bc18f6b39-removebg-preview.png","contentUrl":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2025\/02\/7ae06-be6a6e71-7409-4c8c-bc8b-c64bc18f6b39-removebg-preview.png","caption":"Bahl Fireproofing","inLanguage":"en-US","width":"312","height":"59"},"image":{"@type":"ImageObject","@id":"https:\/\/bahlfireproofing.com\/#logo","url":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2025\/02\/7ae06-be6a6e71-7409-4c8c-bc8b-c64bc18f6b39-removebg-preview.png","contentUrl":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2025\/02\/7ae06-be6a6e71-7409-4c8c-bc8b-c64bc18f6b39-removebg-preview.png","caption":"Bahl Fireproofing","inLanguage":"en-US","width":"312","height":"59"}},{"@type":"WebSite","@id":"https:\/\/bahlfireproofing.com\/#website","url":"https:\/\/bahlfireproofing.com","name":"Bahl Fireproofing","alternateName":"Bahl Fireproofing LLC","publisher":{"@id":"https:\/\/bahlfireproofing.com\/#person"},"inLanguage":"en-US"},{"@type":"ImageObject","@id":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2026\/06\/360da32b-820d-4445-b1e5-a2ad9a5fd33e.png","url":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2026\/06\/360da32b-820d-4445-b1e5-a2ad9a5fd33e.png","width":"2048","height":"2048","caption":"Fireproofing Inspection Checklist for Building Owners","inLanguage":"en-US"},{"@type":"BreadcrumbList","@id":"https:\/\/bahlfireproofing.com\/fireproofing-checklist-for-building-owners\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":"1","item":{"@id":"https:\/\/bahlfireproofing.com","name":"Home"}},{"@type":"ListItem","position":"2","item":{"@id":"https:\/\/bahlfireproofing.com\/blog\/","name":"Blog"}},{"@type":"ListItem","position":"3","item":{"@id":"https:\/\/bahlfireproofing.com\/category\/fireproofing-blog\/","name":"Fireproofing"}},{"@type":"ListItem","position":"4","item":{"@id":"https:\/\/bahlfireproofing.com\/fireproofing-checklist-for-building-owners\/","name":"Fireproofing Inspection Checklist for Building Owners"}}]},{"@type":"WebPage","@id":"https:\/\/bahlfireproofing.com\/fireproofing-checklist-for-building-owners\/#webpage","url":"https:\/\/bahlfireproofing.com\/fireproofing-checklist-for-building-owners\/","name":"Fireproofing Inspection Checklist For Building Owners - Bahl Fireproofing","datePublished":"2026-08-06T10:00:00-05:00","dateModified":"2026-09-25T12:17:36-05:00","isPartOf":{"@id":"https:\/\/bahlfireproofing.com\/#website"},"primaryImageOfPage":{"@id":"https:\/\/bahlfireproofing.com\/wp-content\/uploads\/2026\/06\/360da32b-820d-4445-b1e5-a2ad9a5fd33e.png"},"inLanguage":"en-US","breadcrumb":{"@id":"https:\/\/bahlfireproofing.com\/fireproofing-checklist-for-building-owners\/#breadcrumb"}}]}
```